北 立 传 感
BELEAD SENSOR
BL100IR3
Point 3-IR Flame Detector Datasheet

BeLead Sensor Technology(Wuhan)Co.,Ltd.
BELEAD SENSOR
1 Overview
BL100IR3 point-type 3-IR flame detector (hereinafter referred to as flame detector)provides a
new generation of flame detection capabilities and technical standards.The flame detector uses three low-noise infrared pyroelectric sensors,and then through the built-in 32-bit microprocessor and patent signal processing algorithm,more effectively distinguish the real flame radiation and interference sources,but also greatly reduce the impact of environmental factors on the detector. The detector can set multiple alarm threshold levels to meet the different needs of more
occasions.BL100IR3 flame detector is based on extensive market research and collection of
customer feedback information,through a large number of test data,on the basis of the
widespread application of flame detector in the current market,the hardware circuit integration is higher,and the software algorithm is also greatly improved.
2 Technical parameters
Technical paremeters | |||
Supply voltage | DC24V(range DC18V~30V) | Output | Two relay output |
Monitoring current | ≤35mA(relay) | Fire alarm relay | 1A@30VDC normally open contact capacity |
Field of view | ≤90° | Failure relay | 1A@30VDC normally closed contact capacity |
Alarm threshold | Multiple alarm threshold levels | Operating temperture |
-10℃~55℃ |
Detection distance | ≥30m(0.3m×0.3m g as oline flame) | Operating humidity | 0~95%RH non-condensing |
Response time | ≤20s(0.3m×0.3m gasoline flame) | Storage temperature | -40℃~85℃ |
Spectrum range | Infrared:3.8um-5.3um | Explosion proof level |
EXdICT6 |
Operation instruction | Green LED shining | Electric interface | 1×NPT1/2 |
Alarm instruction | Red LED shining | Protection level | IP66 T80℃ |
Failure instruction | Yellow LED shining | Weight | 0.4KG |
Execuation standard | GB15631-2008 | Enclosure material | Metal |
BELEAD SENSOR
3 Detection distance
Maximum detection distance D(max) | ||
Flame | BL100IR3 Maximum detection distance D(max) | |
Gasoline |
0.1m²brazier(0.3m*0.3m) | 55m |
N-heptane | 55m | |
Alcohol | 50m | |